ProSoft Technology ProLinx-HART Specifications Page 82

  • Download
  • Add to my manuals
  • Print
  • Page
    / 119
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 81
HART ProLinx Gateway Reference
HART Master Driver Manual
Page 82 of 119 ProSoft Technology, Inc.
July 7, 2009
COMMAND 51 - Write Dynamic Variable Assignments
Description
This command sets the assignment of the Dynamic Variables returned with
command 3.
Write Parameters
Word High Byte Low Byte
0
Transmitter Variable Code For Primary
Variable
Transmitter Variable Code For Second
Variable
1
Transmitter Variable Code For Third
Variable
Transmitter Variable Code For Fourth
Variable
Floating Point Data Returned
NONE
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1
Transmitter Variable Code For Primary
Variable
Transmitter Variable Code For Second
Variable
2
Transmitter Variable Code For Third
Variable
Transmitter Variable Code For Fourth
Variable
Page view 81