Prosoft-technology 5205-DFNT-PDPS User Manual Page 33

  • Download
  • Add to my manuals
  • Print
  • Page
    / 61
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 32
Diagnostics and Troubleshooting PDPS ProLinx Gateway
PROFIBUS DP Slave
ProSoft Technology, Inc. Page 33 of 61
December 31, 2008
DP-State
DP-State Machine state
Bits 4,5
00 = 'Wait_Prm' state
01 = 'Wait_Cfg' state
10 = 'DATA_EX' state
11 = Not possible
WD-State
Watchdog-State-Machine state
Bits 6,7
00 = 'Baud_Search' state
01 = 'Baud_Control' state
10 = 'DP_Control' state
11 = Not possible
Baud rate:
The baud rates SPC3 found
Bits
8 to 11
0000 = 12 MBaud
0001 = 6 MBaud
0010 = 3 MBaud
0011 = 1.5 MBaud
0100 = 500 kBaud
0101 = 187.5 kBaud
0110 = 93.75 kBaud
0111 = 45.45 kBaud
1000 = 19.2 kBaud
1001 = 9.6 kBaud
Rest = Not possible
SPC3-Release:
Release no. for SPC3
Bits
12 to 15
0000 = Release 0
Rest = Not possible
Further explanation of Status Register [0]: Word 10309 Bit states
Bit 0
Offline/Passive-idle
0 = SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer
go offline.
1= SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer
are started.
Bit 4, 5
10 = Data Exchange State is Normal. The SPC3 has a correct configuration.
Page view 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 60 61

Comments to this Manuals

No comments