Diagnostics and Troubleshooting DFNT ♦ ProLinx Gateway
Protocol Manual EtherNet/IP Explicit Messaging Client/Server
Page 56 of 124 ProSoft Technology, Inc.
July 24, 2013
4.2 Base Module LEDs
Power is not connected to the power terminals or source is insufficient
to properly power the module (minimum required is 800mA at 24 Vdc)
Power is connected to the power terminals.
A critical error has occurred. Program executable has failed or has
been user-terminated and is no longer running. Press Reset p/b or
cycle power to clear error. If not, use the Debug procedures described
later in this manual.
The unit is in configuration mode. The configuration file is currently
being downloaded or, after power-up, is being read, the unit is
implementing the configuration values, and initializing the hardware.
This will occur during power cycle, or after pressing the reset button. It
also occurs after a cold/warm boot command is received.
An error condition has been detected and is occurring on one of the
application ports. Check configuration and troubleshoot for
communication errors.
This error flag is cleared at the start of each command attempt
(Master/Client) or on each receipt of data (slave/adapter/server); so, if
this condition exists, it indicates a large number of errors are occurring
in the application (due to bad configuration) or on one or more ports
(network communication failures).
4.2.1 Ethernet LED Indicators
No activity on the Ethernet port.
The Ethernet port is actively transmitting or receiving data.
No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.
Physical network connection detected. This LED must be ON
solid for Ethernet communication to be possible.