Page 2 QTS-CLX-PVX September 2009
does not support Control I/O card redundancy
The QTS-CLX-PVX communicates with the ControlLogix processor using scheduled
connections. You configure the module as a Generic Module in RSLogix 5000 with:
250 16-bit words of scheduled input data
248 16-bit words of scheduled output data
250 16-bit words of status input data
The Windows configuration program supplied with the module maps Control I/O bus
data to the scheduled data. It also:
uploads and downloads configuration data
downloads firmware to the module
saves and opens configuration files
exports aliases for use in your RSLogix 5000 application
Firmware Update
The module firmware can be updated using the Windows utility supplied (see page 32).
Part Number
The part number of the module is QTS-CLX-PVX
Module Features
The following figure shows the features of the module.
The module has:
A label that identifies the module, text QTS
Universal Comm
A 4-character scrolling display
3 LEDs, labelled NET, CLX, and OK, to indicate
the status of the I/O bus, the state of the connection
to the ControlLogix processor, and the internal state
of the module
2 BNC connectors to connect to the primary and
secondary I/O bus cables
The module supports insertion and removal under power.