Application Ports S3964R ProLinx Gateway
Driver Manual Siemens 3964R Protocol
ProSoft Technology, Inc. Page 23 of 64
April 14, 2009
3 Application Ports
In This Chapter
Serial Port Cable Connections: Config/Debug and Port 0 .....................23
Cable Connections ................................................................................23
3.1 Serial Port Cable Connections: Config/Debug and Port 0
This section contains information on the cable and pin assignments for the
ProLinx Communication Gateway module application serial ports (RS-
232/422/485).
The module will come with one to five serial ports, depending on the
configuration purchased. In all cases, the protocol serial ports will have the same
pin-outs.
Each serial port is a Mini-DIN physical connection. A 6-inch 'Mini-DIN to DB-9M'
cable is provided for each active protocol port. The DB-9M provides connections
for RS-232, RS-422 and RS-485, as well as for the Debug port. The diagrams in
the following topics detail the pin assignments for several possible physical
connections.
The relationship between the port labeling on the front of the ProLinx module and
the application is as follows:
Port Label Function
Debug Debug/Configuration
Port 0 Application Port 0
3.2 Cable Connections
The application ports on the S3964R module support RS-232, RS-422, and RS-
485 interfaces. Please inspect the module to ensure that the jumpers are set
correctly to correspond with the type of interface you are using.
Note: When using RS-232 with radio modem applications, some radios or modems require
hardware handshaking (control and monitoring of modem signal lines). Enable this in the
configuration of the module by setting the UseCTS parameter to 1.