IEC-101 Slave ProLinx Communication Gateway 101S Protocol Configuration
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 39 of 159
August 6, 2010
2.2.3 Point Count
Point Count configuration ranges in the following configuration items are based
on the assumption that you will be using only one of the available data types for
your application. The number of point counts you configure will have an effect on
gateway performance, in particular, the accuracy of the gateway’s internal clock.
Parameter Description Range
M_SP_NA point count The number of point values assigned in monitored
single-point database.
0 to 1000
M_DP_NA point count The number of point values assigned in monitored
double-point database.
0 to 1000
M_ST_NA point count The number of point values assigned in monitored
step-point database.
0 to 1000
M_BO_NA point count The number of 32-bit values assigned in monitored
bitstring database
0 to 1000
M_ME_NA point count The number of point values assigned in monitored
normalized-point database.
0 to 1000
M_ME_NB point count The number of point values assigned in monitored
scaled-point database.
0 to 1000
M_ME_NC point count The number of point values assigned in monitored
scaled short-float point database.
0 to 50
M_IT_NA point count The number of point values assigned in monitored
counter-point database.
0 to 99
C_SC_NA point count The number of point values assigned in command
single-point database.
0 to 1000
C_DC_NA point count The number of point values assigned in command
dual-point database.
0 to 1000