Prosoft-technology 5201-MNET-101S User Manual Page 50

  • Download
  • Add to my manuals
  • Print
  • Page
    / 159
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 49
101S Protocol Configuration IEC-101 Slave ProLinx Communication Gateway
Protocol Manual IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 50 of 159 ProSoft Technology, Inc.
August 6, 2010
2.18 Group Codes
Note that the highest bit assigns the point to the cyclic data group. This data will
be cyclically reported to the Master at the frequency set in the configuration value
"Cyclic Data Transmission" Parameter.
Group Code Description
0x00000001 Interrogated by general interrogation (station or global)
0x00000002 Interrogated by group 1 interrogation
0x00000004 Interrogated by group 2 interrogation
0x00000008 Interrogated by group 3 interrogation
0x00000010 Interrogated by group 4 interrogation
0x00000020 Interrogated by group 5 interrogation
0x00000040 Interrogated by group 6 interrogation
0x00000080 Interrogated by group 7 interrogation
0x00000100 Interrogated by group 8 interrogation
0x00000200 Interrogated by group 9 interrogation
0x00000400 Interrogated by group 10 interrogation
0x00000800 Interrogated by group 11 interrogation
0x00001000 Interrogated by group 12 interrogation
0x00002000 Interrogated by group 13 interrogation
0x00004000 Interrogated by group 14 interrogation
0x00008000 Interrogated by group 15 interrogation
0x00010000 Interrogated by group 16 interrogation
0x00020000 Interrogated by general counter request
0x00040000 Interrogated by group 1 counter request
0x00080000 Interrogated by group 2 counter request
0x00100000 Interrogated by group 3 counter request
0x00200000 Interrogated by group 4 counter request
0x40000000 Disable event scanning of this point
0x80000000 Periodic/cyclic data returned from unit
If the highest bit (bit 31) is set, data will be produced by the driver for the
specified point at the rate set for periodic data generation. Bit 30 (0x40000000)
enables scanning of this point for event generation. If the bit is clear and the data
type is set for scanning, events will be generated for the point. If the bit is set,
events will not be generated for the point. This feature can be used to select
which points will generate events for the controlling station and can get rid of
event data that is not important to the application
Page view 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 158 159

Comments to this Manuals

No comments