MVI56E-61850S ♦ ControlLogix Platform Contents
IEC 61850 Server Communication Module User Manual
ProSoft Technology, Inc. Page 35 of 81
September 4, 2014
Maximum number of instantiations of this RCB. The matching
Report Control element is generated only if this value is non-
zero.
This number should reflect the number of clients associated to
this report.
The total sum of all values in this column over all lines must not
exceed 8.
The integrity period for this report in milliseconds, at which the
module will send the report to the client associated to this report.
This value may be overridden by the 61850 client during the
report-enable sequence.
0 = Disabled
Number of reconfigurations of the report's associated dataset
Maximum amount of time, in milliseconds, that buffered events
will be held pending before being reported.