Prosoft-technology MVI56E-61850S User Manual Page 56

  • Download
  • Add to my manuals
  • Print
  • Page
    / 81
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 55
Contents MVI56E-61850S ControlLogix Platform
User Manual IEC 61850 Server Communication Module
Page 56 of 81 ProSoft Technology, Inc.
September 4, 2014
6 With the processor in RUN mode in RSLogix 5000, locate the
MVI56E61850S.DATA.DATA_DB.Database.WriteData array.
7 Enter arbitrary values in each of the corresponding tags for the Boolean, Integer, and
Real points configured in PCB.
Boolean: MVI56E61850S.DATA.DATA_DB.Database.WriteData[0].0
Integer: MVI56E61850S.DATA.DATA_DB.Database.WriteData[10]
Real: MVI56E61850S.DATA.DATA_DB.Database.WriteData[40] and [41]
8 Enter the Quality value describing the data integrity of each DO. This memory address
corresponds to the DB Quality Offset parameter in PCB above.
Value
61850 Quality Validity
Descripiton
0
Good
No bit set
1
Questionable
Old data bit set
2
Invalid
Oscillatory bit set
3
Invalid
Old data and oscillatory bits set
9 The MVI56E-61850S ladder logic sends these values over the backplane to the MVI56E-
61850S module memory on every scan.
10 Verify the values of the module memory by viewing the MVI56E-61850S database in the
PCB. For more information, see Using the Diagnostics Menu in ProSoft Configuration
Builder