MVI56E-61850S ♦ ControlLogix Platform Contents
IEC 61850 Server Communication Module User Manual
ProSoft Technology, Inc. Page 55 of 81
September 4, 2014
For Boolean data, enter the following values. One bit of data will be allotted for this DO in
the module's internal memory register 0, bit 0. This location corresponds to
MVI56E61850S.DATA.DATA_DB.Database.WriteData[0].0 in RSLogix 5000.
An (optional) quality byte value is assigned to module memory 100. This location
corresponds to the least significant byte in
MVI56E61850S.DATA.DATA_DB.Database.WriteData[50] in RSLogix 5000.
For Integer data, enter the following values. A 16-bit register will be allotted for this DO in
the module's internal memory register 10. This location corresponds to
MVI56E61850S.DATA.DATA_DB.Database.WriteData[10] in RSLogix 5000.
An (optional) quality byte value is assigned to module memory 110. This location
corresponds to the least significant byte in
MVI56E61850S.DATA.DATA_DB.Database.WriteData[55] in RSLogix 5000.
For Real data, enter the following values. A 32-bit value (stored as two 16-bit registers) will
be allotted for this DO in the module's internal memory register 20. This location
corresponds to MVI56E61850S.DATA.DATA_DB.Database.WriteData[40] and [41] in
RSLogix 5000.
An (optional) quality byte value is assigned to module memory 100. This location
corresponds to the least significant byte in
MVI56E61850S.DATA.DATA_DB.Database.WriteData[60] in RSLogix 5000.
5 Save and download the PCB file to the module. For more information, see Downloading
the Sample Program to the Processor (page 13)