RSLogix Example Program PS69-DPS CompactLogix or MicroLogix Platform
User Manual Profibus DP Slave Communication Module
Page 50 of 108 ProSoft Technology, Inc.
May 9, 2014
3.1 CompactLogix I/O Example
This ladder logic program is a basic example for the setup of the PROFIBUS-DP
Slave communications module "PS69-DPS" in RSLogix5000. This example can
be used to start a project when using a CPU 1769-L32E. Basic PROFIBUS I/O
data exchange is shown. Details on the Subroutines created and the User
Defined Data Types are as follows.
MainRoutine: The MainRoutine calls all of the following routines. This routine
also contains a simple I/O transfer function block.
DPS_Update_Ext_Data: The DPS_Update_Ext_Data routine serves as an
example of how the user can map each of the different extended status
information provided in the ExtStatusInfo array. This routine evaluates the
content of the ExtStaSelect value and copies the information into the
appropriate user defined data type.
SR_Copy_Input: The SR_Copy_Input routine on every scan updates the
DpsInputArray structure with the Input Data of the module.
SR_Copy_Output: The SR_Copy_Output routine on every scan updates the
DpsOutputArray structure with the Output Data of the module.
Numerous user defined data types have been created to make it easier to
address different elements of the Input and Output array of the module. The two
main structures are DpsInputArray and DpsOutputArray. Their definitions and the
structures included in each are shown in the following tables.
The I/O example program can also be used as an example for the two methods
of configuration "Configuration by Master" (ForceMasterConfig) and
"Configuration by Controller Application" (ForceUserConfig). The configuration
array of the sample project is pre-initialized with following values:
Configuration
word
Data
type
Low/High
Byte
Description
Configured
values
Explanation
0
INT
LOW Byte
Busaddress
2
This address will be active if the
rotary switches of the module are
adjusted to "00"
HIGH Byte
Force User
Configuration
0
0 = ForceMasterConfig
The module will take over the
configuration from the master.
1
INT
Reserved
2
INT
Watchdog Timeout
C8h (200dec)
Watchdog 200 ms
3
INT
Number of valid config
bytes
(starting with
Local:1:C.Data[8])
8
8 Bytes of the module definition
array are valid
4
INT
Reserved
5
INT
Reserved
6
INT
Reserved
7
INT
Reserved
8
INT
LOW Byte
Module 1 Type
4
Module 1 Type:
Input Byte with consistency
HIGH Byte
Module 1 Length
3
Module 1 Length: 4 (byte)