Prosoft-technology PS69-DPS User Manual Page 56

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 55
Diagnostics and Troubleshooting PS69-DPS CompactLogix or MicroLogix Platform
User Manual Profibus DP Slave Communication Module
Page 56 of 108 ProSoft Technology, Inc.
May 9, 2014
4.1 Hardware Diagnostics (LED)
The following section contains the LED diagnostic indications and their meaning
for both the CPU in use and the PS69-DPS module.
4.1.1 CompactLogix
The following table shows the possible LED indications of the CompactLogix
CPU module.
Indicator
Color/Status
Description
RUN
Off
No task(s) running; controller in Program mode
Green
One or more tasks are running; controller is in the Run mode
FORCE
Off
No forces enabled
Amber
Forces enabled
Amber Flashing
One or more input or output addresses have been forced to an On or Off state,
but the forces have not been enabled.
OK
Off
No power applied
Green
Controller OK
Red flashing
Recoverable controller fault
Red
Non-recoverable controller fault:
Cycle power. The OK LED should change to flashing red.
If LED remains solid red, replace the controller.
I/O
Off
No activity; no I/O or communications configured
Green
Communicating to all devices
Green flashing
One or more devices not responding
Red flashing
Not communicating to any devices
controller faulted
4.1.2 MicroLogix 1500
To identify problems via possible LED indications of a MicroLogix1500 controller
refer to the MicroLogix1500 User Manuals chapter "Troubleshooting Your
System". Here you will find a detailed description of fault indications and possible
reasons.