PS69-DPS ♦ CompactLogix or MicroLogix Platform RSLogix Example Program
Profibus DP Slave Communication Module User Manual
ProSoft Technology, Inc. Page 51 of 108
May 9, 2014
Module 2 Type:
Input Word with consistency
Module 2 Length: 2 (word)
Module 3 Type:
Output Byte with consistency
Module 3 Length: 4 (byte)
Module 4 Type:
Output Word with consistency
Module 4 Length: 2 (word)
The parameter "ForceUserConfiguration" is initialized with 0. If you want to
activate the pre-defined modules set this parameter to 1. When this parameter is
active the master configuration has to match exactly with this configuration
otherwise the slave will not start the communication with the master.
The parameter busaddress is independent from the parameter
"ForceUserConfiguration". This parameter will be active, if the rotary address
switches of the module are set to "00".