Reference PS69-DPS ♦ CompactLogix or MicroLogix Platform
User Manual Profibus DP Slave Communication Module
Page 96 of 108 ProSoft Technology, Inc.
May 9, 2014
The service code of the
requested object is not
supported
Check parameter of the
CIP Message
The attribute of the
requested object is not
supported
Check parameter of the
CIP Message
Too little data was
transferred with the CIP
Message
Check the "Source
Length" parameter in the
parameter dialog of the
CIP Message, and the
consistency of all length
parameters within the
requested command.
Configuration data size
too large
Too much data
transferred with the CIP
Message
Check the overall length
of the requested
command sent with the
CIP message, and the
consistency of all length
parameters within the
requested command is
correct.
The requested object
does not exist within the
module.
No answer message was
received.
General Error
Non specified error
occurred
General Error
Unknown command /
Invalid Parameter
The values in Requested
Command is unknown or
the parameter of the
requested command are
invalid
The value
Req.Command must be
initialized. For
Read/Write Response
request, check if you
entered the proper Slot,
Index and so on. from
Dpv1StatusRegister
DPS Diagnostic Request
DPS_ERR_DIAG_TOO_LONG
Status data exceeds the length of the diagnostic buffer.
DPS_ERR_NO_FREE_DIAG_BUFFER
No diagnostic buffer available at the moment.
This Error will be temporary.
DPS_ERR_DIAG_DATA_ILLEG_LEN
Mismatch between length of diagnostic block and length at msg.data_cnt.