Page 94 of 108 ProSoft Technology, Inc.
May 9, 2014
CIP MSG Parameterization
Parameter
Value
Remarks
Message Type
CIP Generic
Service Type
Custom
Service Code
64 hex
Service Code "Bridge Message"
Class
65 hex
CIP Object "CIP_MSG_BRIDGE""
Instance
1
Attribute
0
Source Element
Dpv1AlarmReq
Reference to a Tag of type
DPS_DPV1C1_ALARM_REQUEST
Destination
Dpv1AlarmCnf
Reference to a Tag of type
DPS_DPV1C1_ALARM_CONFIRM
Source Length
16 + n
n = Number user specific Alarm Data (0 .. 28)
DPV1 Error Coding Scheme
Error Codes according to the DPV1 specification:
Error Code 1
B7
B6
B5
B4
B3
B2
B1
B0
Error Code (see below)
Error Class (see below)
Error Class
Meaning
Error Code
0 to 9
Reserved
10
Application
0 = Read Error
1 = Write Error
2 = Module Failure
3 to 7 = Reserved
8 = Version Conflict
9 = Feature not Supported
10 to 15 = User Specific
11
Access
0 = Invalid Index
1 = Write Length Error
2 = Invalid Slot
3 = Type Conflict
4 = Invalid Area
5 = State Conflict
6 = Access Denied
7 = Invalid Range
8 = Invalid Parameter
9 = Invalid Type
10 to 15 = User Specific