Prosoft-technology PS69-DPS User Manual Page 89

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 88
PS69-DPS CompactLogix or MicroLogix Platform Reference
Profibus DP Slave Communication Module User Manual
ProSoft Technology, Inc. Page 89 of 108
May 9, 2014
CIP MSG Parameterization
Parameter
Value
Remarks
Message Type
CIP Generic
Service Type
Custom
Service Code
64 hex
Service Code "Bridge Message"
Class
65 hex
CIP Object "CIP_MSG_BRIDGE"
Instance
1
Attribute
0
Source Element
DiagReq
Reference to a Tag of type DPS_DIAGNOSTIC_REQUEST
Destination
DiagCnf
Reference to a Tag of type DPS_DIAGNOSTIC_CONFIRM
Source Length
16 … 48
Corresponds to the size of the DPS_DIAGNOSTIC_REQUEST structure
DPV1 Messaging
This section describes DPV1 messaging functions supported by the PROFIBUS
Slave module.
Note: Every DPV1 read or write request has to be acknowledged by the PLC application program.
Otherwise the PROFIBUS master shuts down communication for both channels, V0 (cyclic IO
data) and V1 (non-cyclic messages). This can cause unexpected lost of data between the master
and the PS69-DPS slave.
DPV1 Class 1 Read Response
The DPV1 Class 1 Read Response message is used by the Slave to reply to a
Master DPV1 Read Request. The MSG instruction Request/Confirmation format
is as follows.
Page view 88
1 2 ... 84 85 86 87 88 89 90 91 92 93 94 ... 107 108

Comments to this Manuals

No comments