Prosoft-technology PS69-DPS User Manual Page 92

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 91
Reference PS69-DPS CompactLogix or MicroLogix Platform
User Manual Profibus DP Slave Communication Module
Page 92 of 108 ProSoft Technology, Inc.
May 9, 2014
DPS_DPV1C1_RW_RESP_CONFIRM
Parameter
Data Type
Value
Meaning
Reserved1
INT
0
Reserved
Reserved2
INT
0
Reserved
Answer
SINT
17
Command for DPV1 Class 1 Read Response
Failure
SINT
0
no error
Reserved4
INT
0
Reserved
RwResp
SINT
2
2 = Write Resp Request. Reply from resp. request
MaAdr
SINT
0.. 125
Bus Address of Master which sent the request. Reply from
resp. request
Slot
INT
0.. 254
Slot Number. Reply from resp. request
Index
SINT
0.. 254
Index. Reply from resp. request
DataLen
SINT
1.. 240
(x)
Length of the data block to be written.
ErrCode1
SINT
E1
DPV1 Error code 1 Reply from resp. request
ErrCode2
SINT
E2
DPV1 Error code 2 Reply from resp. request
Data[1..x]
SINT[1..240]
0-255
DPV1 Write data the Master has sent.
CIP MSG Parameterization
Parameter
Value
Remarks
Message Type
CIP Generic
Service Type
Custom
Service Code
64 hex
Service Code "Bridge Message"
Class
65 hex
CIP Object "CIP_MSG_BRIDGE""
Instance
1
Attribute
0
Source Element
Dpv1RWRespReq
Reference to a Tag of type
DPS_DPV1C1_RW_RESP_REQUEST
Destination
Dpv1RWRespCnf
Reference to a Tag of type
DPS_DPV1C1_RW_RESP_CONFIRM
Source Length
16
Corresponds to the constant size of DPS_DPV1C1_RW
_REQUEST structure
DPV1 Class 1 Alarm Request
The DPV1 Class 1 Alarm Request is used to indicate a DPV1 Alarm to the
connected Master. The MSG instruction Request/Confirmation format is as
follows.