PS69-DPS CompactLogix or MicroLogix Platform Reference
Profibus DP Slave Communication Module User Manual
ProSoft Technology, Inc. Page 79 of 108
May 9, 2014
Byte Offset
Structure member
Data type
Description
Valid Values
32-37
Dpv1StatReg
INT
DPV1 Status Register
See following Table
38-39
Reserved
SINT
Reserved
Reserved
40-135
ExtStatusInfo
SINT[96]
Extended Status
Information
See following section
(*)Note: The status information "InputDataLen" and "OutputDataLen" are related to the definition of
inputs and outputs from point of view of PROFIBUS. There is a clear definition of inputs and
outputs by PROFIBUS. They are always defined from point of view of a PROFIBUS-Master. Do not
confuse them with the input and output area of the communication module. Example: If in status
'OutputDataLen' is indicated a value of 4 Bytes, then it is related to the input area of the
communication module, because the input area of the communication module are outputs from
point of view of a PROFIBUS-Master. The same relation applies to the status 'InputDataLen' and
the output area of the communication module.
TaskState:
Value (hex)
(x =don't care)
Meaning
Description
xxx1
Task is During initialization
If the module remains in this state for more than a few
seconds, the configuration parameters may be invalid.
xx1x
Task running
The module initializatied without error, generally the task is
able to run communication on the bus.
x1xx
Diagnostic
Slave diagnostic telegrams will be sent at the moment on
the bus. Reasons could be the user program (NRDYbit is
set) or the DP master orders this.
1xxx
Data exchange
The data exchange mode is active. The user-data will be
transferred on the bus between the master and the slave
actually.
LastError:
Value
Meaning
Description
52
Invalid bus address
Valid addresses are between 0 and 125
54
Invalid ‚Module Type'
The configured code of the ‚Module Type' parameter is
invalid. If this error happens after a configuration by the
controller application check the configured "ModuleTypes"
also the value "Number of valid config bytes".
55
Invalid ‚ModuleLength'
The configured code for a parameter "ModuleLength" is not
defined.
61
No address-switches available on the
hardware
Please contact your distributor
70
I/O-data too long
The maximum size of I/O-data has been exceeded. Please
check the length of all modules.
71
SPC3/ASPC2 initialization error
The SPC3/ASPC2 returns an error during initialization.
Please contact ProSoft Technical Support.